City of Philadelphia Licensed Electrical Contractor · Lic. #37352

Grounding and Bonding Services in Philadelphia, PA

We test, repair and install grounding and bonding for Philadelphia and Main Line homes and businesses: ground rods, grounding electrode conductors, water and gas pipe bonding, CSST bonding and intersystem bonding, all built to NEC Article 250 by a City-licensed electrical contractor.

A new Siemens 200 amp panel with labeled circuits, a meter socket and a 100 amp disconnect, wired in flexible metal conduit.
Real job
New 200 amp panel and meter socket, grounded and bonded to NEC Article 250
2 rods, 6 ft apartor 25 ohms or less
Lic. #37352
City of Philadelphia L&I
ICC Certified
Commercial Electrical Inspector
NEC Article 250
Grounding & bonding code
5 Service Areas
Philadelphia & the Main Line
Warning Signs

Signs Your Home Needs Grounding or Bonding Work

Grounding and bonding problems hide behind walls and under floors until something goes wrong. These are the signs that tell you to have the system checked by a licensed electrician.

Urgent

A tingle or shock from a faucet, tub or appliance

Metal that shocks you is energized. Stop using it and call right away.

Have it checked

Your water line was replaced with plastic or PEX

If the ground wire was clamped to that pipe, your home may have lost its main grounding electrode.

Have it checked

Two-prong outlets, or three-prong outlets that test open ground

A three-prong outlet does not prove there is a ground behind it.

Have it checked

A surge protector light says not grounded

Most surge protectors need a working ground to divert a spike.

Checking receptacles with a plug-in tester and an Extech circuit analyzer before and after the work.
Real job: testing outlets before and after the work.
Have it checked

Loose, painted or corroded ground clamps

A clamp that turns by hand or shows green corrosion is not a solid connection.

Have it checked

A home inspection flagged missing bonding

Buyers' inspectors often call out missing water or gas bonds.

Have it checked

Yellow CSST gas tubing in the house

Yellow CSST needs its own direct bond back to the electrical system.

Have it checked

Cable or phone lines grounded to a water pipe, or not at all

Communications systems belong on an intersystem bonding termination at the service.

Grounding

Electrical Grounding Services in Philadelphia, PA

Electrical grounding connects your electrical system to the earth, so lightning and utility surges have a path out and the system holds a stable voltage. Our electrical grounding services in Philadelphia start where the service enters the building and follow every conductor to its electrode.

Corrosion and damaged strands at an old meter socket connection, the kind of problem we replace before it fails.
Hazard found on a real job: corrosion and damaged strands at an old service connection.
The grounding electrode system
  1. 01

    Ground rods

    Two 8-foot rods at least 6 feet apart, unless a single rod tests at 25 ohms or less to earth.

  2. 02

    Metal water pipe

    Counts as an electrode only with at least 10 feet of metal pipe in the earth. The connection goes within 5 feet of where it enters, and it always needs a second electrode.

  3. 03

    Concrete-encased electrode

    Rebar or a copper conductor in the footing, where the building has one. An existing one can stay out of the system if the rebar cannot be reached without breaking concrete.

  4. 04

    Grounding electrode conductor

    The wire from the service to the electrodes, sized under NEC 250.66 and protected where it can be damaged.

  5. 05

    What cannot be an electrode

    Metal underground gas piping, and in Philadelphia, aluminum electrodes.

  6. 06

    Before we drive rods

    We contact PA One Call so buried utility lines are marked before any digging.

Bonding

Electrical Bonding Services in Philadelphia, PA

Bonding ties metal parts together and back to the panel. If a hot wire touches a pipe, the current has a low-resistance path home and the breaker trips. Our electrical bonding services cover the water piping, gas piping, communications systems and anything else the code says can become energized, and every electrical bonding installation is sized and clamped to the code.

Metal water piping

What the code asksBonded to the service under NEC 250.104(A)

What we installA sized bonding jumper and listed clamps, with jumpers around water meters where needed

Metal gas piping

What the code asksBonded under NEC 250.104(B), often through the appliance circuit ground

What we installWe confirm the path, or add a bonding jumper

Yellow CSST gas tubing

What the code asksA direct bond, 6 AWG copper or larger, 75 feet or less

What we installA clamp on rigid pipe or a brass CSST fitting, never on the tubing

Cable, phone and satellite

What the code asksAn intersystem bonding termination at the service, NEC 250.94

What we installA listed termination installers can bond to

Pools and hot tubs

What the code asksEquipotential bonding under NEC Article 680

What we installBonding of metal parts, equipment and the water

Building steel

What the code asksInterconnected building frames bonded under NEC 250.104(C)

What we installBonding jumpers sized to the service

CSST rules: ICC CodeNotes, 2021 CSST bonding

For Homeowners

Residential Grounding and Bonding in Philadelphia, PA

Residential grounding and bonding problems in Philadelphia often come from later work: a new plastic water line, a gas line change, a cable install or a panel swap that left the old ground behind.

Fresh service entrance conductors landed in a new Siemens meter socket, ready for the utility meter.

Rowhomes

Service and water lines often enter at the front wall, with little open soil nearby. We plan rod locations around sidewalks, shared walls and buried lines.

Real job photo: New Meter Socket Wiring

An Eaton safety switch mounted on brick with a lockout on the handle, so the power can be shut off at the wall.

Twins and detached homes

More room for rods, and longer runs to them. A service upgrade on these homes in Philadelphia also adds an outdoor emergency disconnect.

Real job photo: Outdoor Safety Disconnect

An old receptacle in a tiled wall with brittle insulation and crowded wiring, pulled out for replacement.

Older homes with two-prong outlets

Two-prong circuits have no equipment ground. The right fix depends on the circuit: a new ground wire, GFCI protection or rewiring.

Real job photo: Hazard Found: Worn Outlet Wiring

Two-Prong Outlets

Three Code-Approved Fixes for Ungrounded Outlets

Swapping a two-prong outlet for a three-prong one without a ground behind it fails inspection and fools surge protectors. These are the three fixes the code allows.

A

Add a ground wire

Run an equipment grounding conductor to the outlet. This gives surge protectors and electronics a true ground.

Best whenWalls or basement ceilings give a clear route
B

GFCI protection

A GFCI outlet or breaker protects people from shock on a two-prong circuit. The outlet is labeled "No Equipment Ground."

Best whenA ground wire is not practical yet
C

Rewire the circuit

Replace old wiring with grounded cable from the panel to every outlet on the circuit.

Best whenThe wiring is brittle, cloth or knob-and-tube
For Businesses

Commercial Grounding and Bonding in Philadelphia, PA

Commercial grounding and bonding in Philadelphia covers more than one ground rod. Transformers, building steel, metal piping, meter centers and long feeders each need the right grounding and bonding path, sized to the equipment and checked by the inspector.

A Siemens meter bank with a service disconnect for each unit: studio, house, first, second and third floors.
Real job: a five-meter bank with a disconnect for each unit.

Service grounding

Electrodes and grounding electrode conductors sized to the service.

Transformers

Separately derived systems with their own bonding jumper and electrode connection, NEC 250.30.

Building steel and piping

Interconnected steel and metal piping bonded back to the service.

Feeder grounding

Equipment grounding conductors sized under NEC 250.122.

Meter centers

Multi-unit services with a disconnect and bonding for each unit.

Isolated ground circuits

Dedicated grounding paths where an equipment maker requires them.

How It Works

How a Grounding and Bonding Job Works

Every job starts by tracing the system you have, so you only pay for what is actually missing.

  1. 01

    Trace the system

    We follow the grounding conductor from the panel to every rod, pipe and clamp.

  2. 02

    Find the gaps

    Missing rods, cut pipes, loose clamps, missing bonds and two-prong circuits get written down.

  3. 03

    Written quote

    You get every fix and the price in writing before work starts.

  4. 04

    Fix and test

    We install the rods, conductors and bonds, test what we touched, and permitted work gets inspected.

Why Us

Licensed Grounding and Bonding Contractors in Philadelphia, PA

Grounding and bonding contractors in Philadelphia must hold a City electrical contractor license. These are the credentials behind our work.

Grounding mistakes stay hidden for years, then show up as a shock, a fried surge protector or a failed inspection. Electrical Hazards, Inc. holds City of Philadelphia electrical contractor license #37352, and an ICC Certified Commercial Electrical Inspector on our team checks grounding and bonding the way an inspector will.

#37352
Philadelphia electrical contractor license
ICC Certified Commercial Electrical Inspector badge
ICC
Certified Commercial Electrical Inspector on our team
EPA Lead-Safe Certified Firm badge, NAT-F164781-2
EPA
Lead-Safe Certified Firm NAT-F164781-2
NEC 250
Grounding and bonding built to the code article
Pricing

What Grounding and Bonding Work Costs

Grounding and bonding work is priced by what is missing. Most jobs fall into one of these three scopes, and you get the exact fixes and price in writing before any work starts.

Scope 1

Bond or clamp repair

  • Replace a loose or corroded clamp
  • Add a water or gas pipe bond
  • Add a jumper around the water meter
Scope 2

Electrode upgrade

  • Drive new ground rods
  • Install a new grounding electrode conductor
  • Add an intersystem bonding termination
Scope 3

Full system with service work

  • Grounding and bonding redone with a panel or service upgrade
  • Outdoor disconnect where the code requires it
  • One shutoff for both jobs
Verified Reviews

What Our Customers Say

Real reviews from our customers on Networx.

“Good work, reasonable, prompt AND pleasure to work with. Highly recommended.”

Job: Outlets, GFCIs, meter box and breakers to bring an old house up to code

ML
Marc L.
Philadelphia, PA

“TOTALLY SATISFIED. Great price, work was completed on time and very professional.”

Job: New 220-volt line

S
Sean
Philadelphia, PA

“It's all I was looking for: great price, professional, and done right…”

Job: 220-volt line

S
Sean
Philadelphia, PA · repeat customer
Service Area

Grounding and Bonding Across Philadelphia and the Main Line

We work across four counties and file with the permit office for each address.

Philadelphia
L&I permit, licensed inspection agency
Lower Merion
Lower Merion Township
Upper Merion
Upper Merion Township
Wayne
Radnor, Tredyffrin or Upper Merion, by address
Berwyn
Tredyffrin or Easttown, by address
Need to Know

Grounding and Bonding FAQs for Philadelphia

63 questions homeowners and building owners ask us most. Filter by topic, or search if you already know what you need.

What is the difference between grounding and bonding?

Grounding connects the electrical system to the earth through electrodes like ground rods. Bonding connects metal parts to each other and to the panel so a fault trips the breaker. A safe system needs both.

How many ground rods does my house need?

Two rods at least 6 feet apart, unless a single rod tests at 25 ohms or less to earth. A metal water pipe electrode also needs a second electrode.

My plumber replaced the water line with plastic. Is my house still grounded?

Maybe not. If the ground wire was clamped to the old metal pipe, it may now lead nowhere. We check it and add ground rods if needed.

Do you do commercial grounding and bonding?

Yes, including service grounding, transformer grounding, building steel and piping bonds, and feeder grounding for storefronts, offices and multi-unit buildings.

Why does a house need grounding?

It gives lightning and utility surges a path to earth and keeps the electrical system at a stable voltage relative to the ground.

Does the ground rod make a breaker trip?

No. Bonding and the equipment grounding conductors do that work. The earth path has too much resistance to trip a breaker reliably.

What is a grounding electrode conductor?

The wire from your service to the electrodes, sized to the service under NEC 250.66.

Is the green or bare wire the ground?

That is the equipment grounding conductor. It bonds outlets, fixtures and appliances back to the panel.

Is a tingle in the shower dangerous?

Yes. Any tingle from water or metal fixtures means current is where it should not be. Treat it as urgent.

What does "open ground" on an outlet tester mean?

The outlet has no working connection to the equipment grounding conductor. It may be a two-prong circuit, a loose wire or a broken path.

My home inspection says bonding is missing. Is that serious?

It is a real safety item and a common inspection note. Most missing bonds are fixed in one visit.

How deep do ground rods go?

A standard rod is 8 feet long and is driven its full length into the earth.

Can my metal water pipe be my ground?

Only with at least 10 feet of metal pipe in the earth, and it must always be supplemented by another electrode, usually ground rods.

What is a Ufer ground?

A concrete-encased electrode: rebar or a copper conductor in the footing. Newer buildings often have one.

What size ground wire do I need?

The grounding electrode conductor is sized to your service conductors under NEC 250.66.

What gets bonded in a house?

Metal water piping, metal gas piping, communications systems through an intersystem bonding termination, and pools or hot tubs if you have them.

Does black CSST need bonding?

Black arc-resistant CSST certified to CSA/ANSI LC-1 does not need the extra direct bond, unless the system also has yellow CSST.

Why does a water meter need a jumper?

A jumper around the meter keeps the bonding path continuous if the meter is removed or has plastic parts.

Do pools and hot tubs need bonding?

Yes. NEC Article 680 requires equipotential bonding of metal parts, equipment and the water for permanently installed pools and many hot tubs.

Do older Philadelphia homes have grounding problems?

Often. Two-prong circuits, clamps on pipes that were later replaced, and no intersystem bonding are common. We check all three.

Should grounding be checked before solar or an EV charger?

Yes. Both depend on a sound grounding and bonding system, so we check it first and fix what is missing.

Is a GFCI outlet the same as a ground?

No. A GFCI protects people from shock, but it does not give electronics or surge protectors a ground.

Do twins and detached homes need an outdoor disconnect?

In Philadelphia, a new service or service upgrade on these homes adds an outdoor emergency disconnect. Attached rowhomes of three stories or less are exempt.

Do transformers need their own grounding?

Yes. A transformer creates a separately derived system, which needs its own system bonding jumper and grounding electrode connection under NEC 250.30.

What is an isolated ground receptacle?

An outlet with a separate grounding path, used when an equipment maker requires it. It is still part of the grounding system, not a separate earth ground.

Do commercial grounding jobs need permits and plans?

Grounding done as part of a service upgrade needs plans in Philadelphia. Smaller corrections can fall under a simpler permit. We confirm the path before work starts.

What affects the cost of grounding work?

Whether rods are needed, the size and length of the grounding conductor, how many bonds are missing, access to soil and piping, and whether the work is part of a service upgrade.

Do I need a permit for grounding work?

Grounding done with a panel or service job is covered by that permit. We tell you whether a standalone repair needs its own.

Do you give a written quote?

Yes, with every fix listed before work starts.

What should I have ready for the visit?

Access to the panel, the electric meter, the water line where it enters, the gas meter and any inspection report.

Do you test the outlets after the work?

Yes. We test the outlets and connections we worked on before we leave.

How do I book a grounding and bonding check?

Call (267) 977-2106 or send the form below. We call you back to set up a visit.

How do I know if my house is properly grounded?

A three-prong outlet does not prove it. An electrician traces the grounding conductor from the panel to the rods or water pipe, checks every clamp and tests the outlets.

Does my gas line need to be bonded?

Yes. Metal gas piping must be bonded, often through the equipment ground of the appliance circuit. Yellow CSST needs its own direct bond.

Can I replace two-prong outlets with three-prong outlets?

Only if there is a ground to connect, or with GFCI protection and a "No Equipment Ground" label. A three-prong outlet with no ground behind it gives false confidence.

How much does grounding and bonding work cost?

It depends on what is missing: a single bond or clamp, new rods and a grounding conductor, or a full system redone with a service upgrade. You get a written price after we trace the system.

Why does a house need bonding?

If a hot wire touches a metal pipe or box, bonding gives that current a low-resistance path back to the panel so the breaker trips. Without it, the metal can stay energized.

What is a grounding electrode?

The part that connects to the earth: ground rods, a metal underground water pipe, a concrete-encased electrode in the footing, a ground ring or plates.

Which part of the code covers grounding and bonding?

Article 250 of the National Electrical Code. Philadelphia's EZ standard for residential service equipment cites the 2020 NEC.

I got a shock from my faucet. What should I do?

Stop using it and call an electrician right away. A shock from metal plumbing means something is energized.

Why does my surge protector say it's not grounded?

Its outlet may have no ground, or the ground path is broken somewhere between the outlet and the panel. We trace it and fix the break.

Can bad grounding cause flickering lights?

A loose neutral is a more common cause, and the two can show up together. Flicker plus shocks or warm outlets needs a visit soon.

Can bad grounding damage electronics?

It can make surge protection work poorly, which leaves electronics more exposed to voltage spikes.

Why do I need two ground rods?

The code requires a second rod unless a single rod tests at 25 ohms or less to earth. Two rods spaced at least 6 feet apart meet the rule without the test.

Can gas pipe be used as a ground?

No. Metal underground gas piping is not allowed as a grounding electrode.

Can you install ground rods at a rowhome?

Usually, where we can reach soil near the service. We plan around sidewalks, shared walls and buried lines, and contact PA One Call before driving rods.

Do ground rods and clamps wear out?

Clamps can loosen and both can corrode. We check each connection and replace what is damaged.

What is CSST and why does it need bonding?

Corrugated stainless steel tubing is flexible gas line. Yellow CSST needs a direct bond of 6 AWG copper or larger, 75 feet or less, clamped to rigid pipe or a brass fitting.

What is an intersystem bonding termination?

A bonding point at the service, required by NEC 250.94, where cable, phone, satellite and other low-voltage installers bond their systems.

Does a water heater need a bonding jumper?

Not always. If dielectric fittings or plastic connectors break the metal path between the hot and cold piping, a jumper keeps the hot side bonded.

Where does the gas bonding clamp go?

Downstream of the gas meter, on rigid pipe or a brass CSST fitting, never on the corrugated tubing itself.

Will a panel upgrade fix my grounding?

It is the right time to bring grounding and bonding up to code, and the inspector checks it. We include it in the panel upgrade scope.

Can you add a ground to a two-prong outlet?

Yes, by running an equipment grounding conductor to it. If that is not practical, GFCI protection is a code-approved option.

Did the cable company ground its line correctly?

Installers should bond to an intersystem bonding termination. Older homes often show cable grounds clamped to a water pipe instead, which we correct.

What does commercial grounding and bonding include?

Service grounding, grounding and bonding for transformers, bonding of building steel and metal piping, and equipment grounding for feeders and branch circuits.

Does building steel need bonding?

Interconnected structural steel that forms the building frame must be bonded under NEC 250.104(C).

Do you work on multi-unit buildings?

Yes, including meter centers with a disconnect for each unit and the bonding between them.

Can you fix grounding items from a commercial inspection report?

Yes. Send us the report and we quote each item.

Is a bonding repair a big job?

Replacing a clamp or adding a water or gas bond is usually small. New rods, a new grounding conductor and an intersystem bonding termination take more.

Who inspects grounding work in Philadelphia?

A licensed electrical inspection agency inspects permitted work, and the City issues a Certificate of Approval once it passes.

Can you do grounding work during a panel upgrade?

Yes, and it saves a second visit, since the service is already shut off.

Will my power be off during the work?

A bond or clamp repair usually needs no outage. Replacing the grounding electrode conductor may need a short service shutoff.

Which areas do you serve?

Philadelphia, Lower Merion, Upper Merion, Wayne and Berwyn, plus nearby Main Line towns.

Showing 12 of 63

Free Quote

Book a Grounding and Bonding Check

Electrical Hazards, Inc. will call you back, trace your grounding and bonding, and put every fix and the price in writing before any work starts.

License
Philadelphia #37352

We use your details only to reply to this request.

Call Free Quote